RE-2Y(St)YSWAY-fl

Application: 

These cables are generally employed in instrumentation and control systems, analog and digital signal transmission of chemical and petrochemical industrial premises, power plants, natural gas and petroleum industries, etc. Direct connection is not permitted under ambient with a low impedance sources. Cables with blue sheaths are suitable for security system applications. The cable armour protects the cable against mechanical impacts. Furthermore, these cables can directly be buried in the soil. They are suitable in dry and wet indoor and outdoor installations.

Conductor material: Electrolytic stranded annealed copper wire (IEC 60228, Class 2)
Communication core: 0,50 mm² (7×0,30 mm) tinned or annealed stranded
copper, PE or XLPE insulated orange core. Screened
pair cores are strand communication core with
together twisted layers. Fixed with PES tape.
Insulation: PE (EN 50290-2-23)
Overall screening: (St) – 100% Coverage AL-PES tape and 0,50 mm²
(7×0,30 mm) tinned strand drain wire with screened.
Inner sheath: Y – PVC sheath (EN 50290-2-22)
Armoring: SWA – Round galvanized steel wire armors
Outer sheath: Y – PVC Sheath (EN 50290-2-22), RAL 9005 Black,
RAL 5015 Blue or RAL 7001 Grey
Flame retardant: (for a single cable) IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2
Flame retardant: (for a bunch cable) IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24
Oil resistance: ICEA S-82-552
UV resistance: Only valid for Black sheath cables
Temperature range (°C): Fixed: -30 °C +70 °C
Flexible: -5 °C +50 °C
Min. bending radius (mm): 10 x D
Nominal voltage U: 300 V 500 V
Cross section (mm²): 0,50 0,75 1,00 1,30  1,50 2,50 0,50 0,75 1,00 1,30  1,50 2,50
Conductor DC resistance (Ω/km): 36,8 25,00 8,51  4,21  2,30  7,56 36,8 25,00 8,51  4,21  2,30 7,56
Capacity (800 MHz) (pF/m): PVC: < 250 PE ve XLPE : < 150 PVC: < 250 PE ve XLPE : < 150
Operating voltage: Max. 300 V Max. 500 V
Test voltage (V ac) 1 minutes: 1000 2000