N2XS2Y

Application: 

For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the PE sheath permits strong mechanical stress during installation or during operation.

Conductor material:  Bare copper
Conductor construction:  Class 2
Insulation: XLPE DIX 8
Sheathing material: Polyethylene DMP2
Colour of outer sheath: Black
Flame retardant: No
Maximum temperature at conductor: 90 °C
Maximum operating temperature, fixed: 70 °C
Temperature, moved/during installation: -20 / +70 °C
Bending radius, fixed installation: 15 x Da
Partial discharge: 2 pC
Voltage levels: N2XS2Y 6/10 kV N2XS2Y 12/20 kV N2XS2Y 18/30 kV
Nominal voltage Uo: 6 kV 12 kV 18 kV
Nominal voltage U: 10 kV 20 kV 30 kV
Maximum permitted operating
voltage in 3-phase systems:
12 kV 24 kV 36 kV
Test voltage: 21 kV 42 kV 63 kV