XHP-48 / N2XSY

For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The good installation properties of this cable make installation easy, even on difficult routes. Acc. to VDE 0276-603 cables must be protected against direct sun irradiation.

Share:

SKU: EMP11008 Category:

Description

For fixed installation in buildings, in free air, in ground for direct burial and in water as it is the flame retardant according to IEC60332-1. Cable includes UV protection.

Additional information

Conductor material

Bare copper

Conductor construction

Class 2

Insulation

XLPE DIX 8

Sheathing material

Color of outer sheath

Flame retardant

VDE 0482-332-1-2/IEC 60332-1

Maximum temperature at conductor

90 °C

Maximum operating temperature, fixed

Temperature, moved/during installation

-5 / +70 °C

Bending radius, fixed installation

15 x DA

Partial discharge

2 pC

Voltage levels

XHP-48 6/10 kV / XHP-48 12/20 kV / XHP-48 18/30 kV

Nominal voltage Uo

6 kV / 12 kV / 18 kV

Nominal voltage U

10 kV / 20 kV / 30 kV

Maximum permitted operating voltage in 3-phase systems

12 kV / 24 kV / 36 kV

Test voltage

21 kV / 42 kV / 63 kV