NA2XS(FL)2Y

For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high durability of laminated polyethylen sheat permits strong mechanical stress during installation or operation. Longitudinally and radially watertight avoids water propagation inside the cable.

Share:

SKU: EMP11015 Category:

Description

For fixed installation in buildings, in free air, in ground for direct burial and in water as it is the flame retardant according to IEC60332-1. Cable includes UV protection.

Additional information

Conductor material

Aluminum

Conductor construction

Class 2

Insulation

XLPE DIX 8

Bonded sheath

Yes

Transverse water-tight

Yes

Longitudinally water-tight

Yes

Color of outer sheath

Meter mark

Yes

Flame retardant

No

UV-resistant

Maximum temperature at conductor

90 °C

Maximum operating temperature, fixed

Temperature, moved/during installation

-20 / +70 °C

Bending radius, fixed installation

15 x DA

Partial discharge

2 pC

Voltage levels

NA2XS(FL)2Y 6/10 kV / NA2XS(FL)2Y 12/20 kV / NA2XS(FL)2Y 18/30 kV

Nominal voltage Uo

6 kV / 12 kV / 18 kV

Nominal voltage U

10 kV / 20 kV / 30 kV

Maximum permitted operating voltage in 3-phase systems

12 kV / 24 kV / 36 kV

Test voltage