N2XS2Y

For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the PE sheath permits strong mechanical stress during installation or during operation.

Share:

SKU: EMP11010 Category:

Description

For fixed installation in buildings, in free air, in ground for direct burial and in water as it is the flame retardant according to IEC60332-1. Cable includes UV protection.

Additional information

Conductor material

Bare copper

Conductor construction

Class 2

Insulation

XLPE DIX 8

Sheathing material

Color of outer sheath

Flame retardant

No

Maximum temperature at conductor

90 °C

Maximum operating temperature, fixed

Temperature, moved/during installation

-20 / +70 °C

Bending radius, fixed installation

15 x DA

Partial discharge

2 pC

Voltage levels

N2XS2Y 6/10 kV / N2XS2Y 12/20 kV / N2XS2Y 18/30 kV

Nominal voltage Uo

6 kV / 12 kV / 18 kV

Nominal voltage U

10 kV / 20 kV / 30 kV

Maximum permitted operating voltage in 3-phase systems

12 kV / 24 kV / 36 kV

Test voltage

21 kV / 42 kV / 63 kV