LiHCH FE180/PH90

Application: 

Indoor instrumentation and control cabling, for electrically noisy environments, fire alarm systems in office buildings.

 
Conductors: Stranded copper conductors per IEC 60228
Insulation: Cross-linked ceramic forming polymer compound
Core: Layout in concentric layers
Core wrapping:  Polyester tape + fiberglass tape
Screen: Tinned copper braiding (min. 85% coverage)
Outer jacket: HFFR per EN 50290-2-27, Color: orange
Insulation dielectric strength: 2000 VAC(50 Hz) / 1 minute
Insulation resistance: 20 MΩ.km
Voltage rating: 300 V
Bending radius: > 7.5 x cable diameter
Operation temperature range: -40 ºC to +90ºC
Single cable flame retardance: IEC 60332-1
Bundled cables flame retardance: IEC 60332-3-24
Smoke emission: IEC 61034-2
Halogen gas content: IEC 60754-1
Corrosive gas emission: IEC 60754-2
Circuit integrity: FE 180 per IEC 60331-23
Circuit integrity under shock: PH90 per EN 50200