Proizvodi
Tehnički predlog
LiHCH FE180/PH90

Application:
Indoor instrumentation and control cabling, for electrically noisy environments, fire alarm systems in office buildings.
Conductors: | Stranded copper conductors per IEC 60228 | |
Insulation: | Cross-linked ceramic forming polymer compound | |
Core: | Layout in concentric layers | |
Core wrapping: | Polyester tape + fiberglass tape | |
Screen: | Tinned copper braiding (min. 85% coverage) | |
Outer jacket: | HFFR per EN 50290-2-27, Color: orange | |
Insulation dielectric strength: | 2000 VAC(50 Hz) / 1 minute | |
Insulation resistance: | 20 MΩ.km | |
Voltage rating: | 300 V | |
Bending radius: | > 7.5 x cable diameter | |
Operation temperature range: | -40 ºC to +90ºC | |
Single cable flame retardance: | IEC 60332-1 | |
Bundled cables flame retardance: | IEC 60332-3-24 | |
Smoke emission: | IEC 61034-2 | |
Halogen gas content: | IEC 60754-1 | |
Corrosive gas emission: | IEC 60754-2 | |
Circuit integrity: | FE 180 per IEC 60331-23 | |
Circuit integrity under shock: | PH90 per EN 50200 |