JE-H(St)H FE180/E30-E90 BMK

Application: 

For signal transmission between electronic devices, in computer systems of process control units in fire endangered areas with high person or real value concentration, for installation of circuits with circuit integrity E30/E90 according to DIN 4102 part 12, with tested cable systems. For fixed installation in dry and damp areas on certified carrier systems. By the special sheath printing this cable is particularly designed for the use in fire signalization systems.

Conductor material:  Bare copper
Insulation:  FRNC compound HI1
Screen: Foil
Drain wire: Yes
Sheathing material:  FRNC compound HM2
Color of outer sheath: Red
Flame retardant: VDE 0482-266-2-4/IEC 60332-3-24 (Kat. C)             
Smoke density: DIN EN 61034/IEC 61034
Halogen free: DIN EN 50267/IEC 60754
Fire resistance: FE 180 (IEC 60331)
Circuit integrity: E30-E90
Maximum operating temperature, fixed: -5 / +50 °C
Operating capacity: 120 nF/km
Core identification:  Colors + rings

Additional information: Stranding: cores twisted into pairs, 4 pairs laid up into sub-units (2-pairs cable stranded as one starquad), sub-units laid up in layers. Core identification: The basic color of each bunch is continuous sequence: blue, red, grey, yellow, green, brown, white, black. The bundles are identified by the color of the rings on the insulation.